EX-150 SGO Print E-mail

EX Gas/Oil Series - High Pressure Steam Boiler

Miura’s exclusive “low water content, watertube” design is the most versatile boiler available in the marketplace today. A once-through, forced circulation steam boiler producing steam in just 5 minutes while maintaining an 85% fuel-to-steam efficiency.
A once-through, forced-flow, steam generator design provides full output within 5 minutes.

  • Gas-Oil dual fuel burner
  • Up to 300BHP per boiler and up to 4,500 HP (150,000lb/hr) with our MI-system
  • Up to 250psi pressure boiler is available.
SpecificationsDimensions and Schematic Note
Specifications
EX-150 SGO
Boiler Type No 2 Oil Fired, Natural Gas or Propane Fired with Economizer
Utilization Horsepower 150 HP
Maximum Pressure 170 psig MAWP
Equivalent Output 5,175 LB/HR
Heat Output 5,022,000 BTU/HR
Efficiency 85% (80% without Economizer) - fuel to steam
Heating Surface Area 323 FT²
Operational Weight 11,500 LBS
Shipping Weight 10,650 LBS
Dimensions Given are Approximate
Width 90 in.
Length 130 in.
Height 127 in.
Combustion System Proprietary forced draft, step fired modulation Hi-Low-Off
Ignition System Electric spark ignited, interrupted gas pilot
Power Supply 208, 230, 460, 575 V, 3 Phase, 60 Hz
Max. Electrical Consumption 24.5 KVA (25.4 for oil)
Fuel Type Natural gas or propane (3-5 psig), No. 2 oil
Gas Consumption 5,880 SCFH
No.2 Oil 42.2 GAL/Hr
Gas Supply Pressure 3-5 psig natural gas or propane
Main Steam Outlet Valve 3 in.
Safety Valve Outlet One 2 1/2 in.
Main Water Inlet 1 in.
Fuel Gas Inlet 2 in.
Fuel Oil Inlet 3/4 in.
Automatic Surface Blowdown One 3/8 in.
Manual Blowdown Two 1 in.
Chimney Diameter (ID) 20 in.
Flame Detector Ultraviolet flame eye sensor
Pressure Control Adjustable pressure transducer and switch
Liquid Volume Control Electric Conductivity Type
Overheat Protection Low Water Cut Off Thermocouple
 
Sitemap        © 2008 Miura Boiler, Inc.